Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
1. 3-way valve not opened 2. Outdoor unit ambient temperature too low
3. Outdoor unit fan operation defective, foreign matter at heat exchanger
4. EEV defective, strainer clogged 5. Solenoid valve defective 6. 4-way valve defective
7. Low pressure sensor characteristics defective 8. Insufficient refrigerant
Suction pressure sensor
"Protection stop by "suction pressure 15psi (0.10MPa)continued for 10 minutes"
or "suction pressure 7.25psi (0.05MPa)" during operation of any compressor""
was generated 5 times within 3 hours
No foreign matter in air passage?
Heat exchange fins clogged
Fan rotates?
Outdoor unit fan motor check
Check Point 3 :
Check the outdoor unit fan operation, heat exchanger
Check Point 2 : Check the outdoor unit ambient temperature
Outdoor ambient temperature lower than operating range?
Outdoor unit EEV1, EEV2 operation check
Strainer not clogged?
Refer to "Service Parts Information 14,15 ".
Check Point 4 : Check the outdoor unit EEV, strainer clogging
Indoor unit EEV operation check
Strainer not clogged?
Check Point 4 : Check the indoor unit EEV, strainer clogging
Suction pressure sensor characteristics check
* For the characteristics of the suction pressure sensor,
refer to "Service Parts Information 22".
Check Point 7 : Check the suction pressure sensor
Check Point 8 : Check the refrigerant amount
Leak check
Check Point 6 : Check the solenoid valve (SV1)
Solenoid valve operation check
Refer to "Service Parts Information 17".
Check Point 1 : Check if 3-way valve is open.
If the 3-way valve was closed, open the
3-way valve and check operation.
Check Point 1 : Check if 3-way valve is open.
If the 3-way valve was closed, open the
3-way valve and check operation.
OK
OK
OK
OK
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
<Cooling
operation>
<Heating
operation>
Check Point 5 : Check the 4-way valve (4WV1, 4WV2, 4WV3)
4-way valve operation check.
Refer to "Service Parts Information 18".
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A 5. 1
Error Code : 9 U / A 6
Indicate or Display:
Trouble shooting 65 EA5. 1
OUTDOOR UNIT Error Method:
Low Pressure Abnormal
04-77
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......