3-6 FUNCTION
03-16
3-6-1 Auto Restart
The air conditioner restarts with the previous setting operation.
3-6-2 Icing Protection Control
3-6-3 Oil Recovery Operation
[Oil recovery operation] : It periodically returns the residual refrigerant ion oil in the indoor unit and the connection
piping back to the outdoor unit , and prevents the compressor oil level from decreasing.
6 sec ON 2 sec OFF Blinking
Indoor unit LED : Operation LED
Indoor fan : Same operation before oil recovery operation.
Indoor EEV : Control pulse
During the above operation, a refrigerant noise may be from the indoor unit.
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition
Compressor is operation more than 3 minutes.
When "Heat exchanger inlet temperature T
A
" continues *4 minutes or more.
Compressor is operation more than 3 minutes.
When "Heat exchanger outlet temperature T
A
" continues 4 minutes or more.
(2) Operation
EEV is closed.
Fan is at the setting amount.
(3) Completing Condition
Heat exchanger inlet and middle temperature T
B
After more than 5 minutes
*
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
T
A
T
B
1°C
7°C
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......