Trouble shooting 8 E14. 5
OUTDOOR UNIT Error Method:
The number of Indoor unit shortage
Error
Indicate or Display:
Outdoor Unit : E.1 4. 5
Error Code : 9 U / 1 4 / 1 6 / 1 4. 5 / 1 4. 3 *
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When the indoor unit number decreases for 180 seconds from the memorized
maximum indoor units number after power(Breaker) ON.
Communication PCB connection check
Communication PCB check
Communication line connection, open check
Check Point 5 : Check the communication PCB
(indoor unit/ outdoor unit)
1. Indoor unit power off 2. Noise, momentary open, voltage drop
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective
6. Controller PCB defective
Check Point 2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Check the indoor unit
power supply
Main power ON check
Power cable connection and open check
Check Point 3 : Check the communication line connection
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
Check Point 6 : Replace Main PCB and Communication PCB
(indoor unit/ outdoor unit)
Change Main PCB and Communication PCB, and set up the original address.
Forecast of Cause :
Check Point 1 : Find the indoor unit that the communication is lost.
Check system drawing and service tool.
OK
OK
OK
OK
OK
OK
Attention!!
In case of DIP-SW SET4-1 is ON(factory setting),
If this error occurs, system stops.In case of
DIP-SW SET4-1 is OFF,
If this error occurs, system does not stop.
If the failure indoor unit is pinpointed and it
needs to erase the error indication, it can be
reset by function setting (F3-41: Maximum
memorized indoor unit number reset).
Caution!!
Even if normal, this error occurs temporarily by
the timing of the power ON of outdoor unit,
indoor unit, and signal amplifier.
In this case, please wait for 5 minutes after
turning on all the equipments.
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash. /
No display (When DIP-SW4-1 is OFF.)
Refer to SERVICE INFORMATION Network communication Abnormal
*Peripheral device indicates 14,16
04-17
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......