Trouble shooting 88
Peripheral device FAN not operate
OK
LED ON
LED Blinking
Forecast of Cause :
1. Power supply failure 2. Trouble on peripheral device
3. DX-Kit Electrical compornent defective 4. Field setting mismatch
Check Point 1 : Power supply
Check Point 2 : LED indication on the controller PCB
Check Error code indication on the
remote controller or Service tool
Is not the breaker down?
Instant drop ---------------------- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line
(Neon bulb or electric equipment that may cause harmonic wave).
Check the complete insulation of grounding.
Check circuit on the terminal ON /OFF SIGNAL(OUTPUT)
04-97
Short circuit
Short circuit
Refer to the service manual for
the peripheral device
and check the trouble shooting tips.
Check Point 3 : Operation signal output
Check circuit on the terminal FAN SIGNAL (OUTPUT)
Check Point 4 : FAN SIGNAL output
Open circuit
Open circuit
Check power input CN800 Pin1 - Pin2
OK (DC12V)
Make sure that the operation command
(ON signal) is transfering from the controller to
the DX-Kit controller.
If the ON singal was OK, Replace the Relay PCB.
Check Point 5 : Relay PCB power input DC12V
Other tips
NG
Make sure that the operation command (ON signal) is
transfering from the Controller to the DX-Kit controller.
If the ON singal was OK, Replace the Main PCB.
Check Field function setting, (External input signal setting)
The Prohibit setting condtions
The operating mode mismatch
General check procedure
1. Check Error code on the VRF system. (Remote controller, Service tool, etc)
2. Check LED brinks on the controller PCB of DX-KIT
3. Check Error code on the peripheral device.
4. Check non of wrong filed settings or wrong installation.
5. Check if FAN operation stopped by the freeze prevention or the defrosting operation.
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......