![Fujitsu AB* A12GATH Service Manual Download Page 178](http://html.mh-extra.com/html/fujitsu/ab-a12gath/ab-a12gath_service-manual_117995178.webp)
1. Stop the operation, and turn off the all outdoor units. (Make sure the pressure equalization has been finished)
1-2. Backup operation when compressor of the slave unit #1 is broken.
[Procedure]
(Example: Three outdoor units are connected. the slave unit #1 is broken.)
2. Fully shut off the 3-way valve (Liquid, Gas) of the broken slave unit #1.
3. Make up the system of two outdoor units (master and slave) by changing the DIP SW of the master unit.
4. Set up the slave unit #2 as Slave unit #1.
6. Turn on the units except the broken slave unit, and wait for more than 30 seconds.
(Do not turn on the broken slave unit)
7. It is ready for Backup operation.
Start operation as usual.
Change the DIP SW 3-3/ 3-4 (Number of slave units connected) of the master unit,
from [ON/OFF](two units) to [OFF/ON](one unit).
Change the DIP SW 3-1/ 3-2 (Outdoor unit address setting) of the slave unit #2,
from [ON/ OFF](slave unit #2) to [OFF/ ON](slave unit #1).
5. Change the DIP SW 5-1/ 5-2 (Number of outdoor unit) of the master unit and the slave
unit #2 (substitutional slave unit #1), from [ON/ OFF](three) to [OFF/ ON](two).
04-102
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......