01-08
Check Item
Check contents
Judgement
Present Status
Ref. circuit name: ____________________________, Ref. address :________(00 99)
Additional
Charged
Refrigerant
Outdoor Unit
OU Model Name
Additional Refrigerant Amount for OU
AJ* 072L / AJ* 090L / AJ* 108L
AJ* 126L / AJ* 144L / AJ* 162L
AJ* 072L / AJ* 090L : 0 (kg)
AJ* 108L / AJ* 126L / AJ* 144L / AJ* 162L : 3.3 (kg)
(kg)
Connecting
Pipe
Liquid Pipe Length
Additional Refrigerant Amount based on the liquid pipe length
@ 6.35mm
(m)
For pipe diameter
6.35mm : 0.021 kg/m
For pipe diameter
9.52mm : 0.058 kg/m
For pipe diameter 12.7mm : 0.114 kg/m
For pipe diameter 15.88mm : 0.178 kg/m
For pipe diameter 19.05mm : 0.268 kg/m
(kg)
@ 9.52mm
(m)
(kg)
@ 12.7mm
(m)
(kg)
@ 15.88mm
(m)
(kg)
@ 19.05mm
(m)
(kg)
Total Additional Amount of Charged Refrigerant
(kg)
Note: In the refrigerant system, overall refrigerant amount 31.5 kg (for 1 OU), 63.0 kg (for 2 OUs) and 94.5 kg (for 3 OUs)
Overall refrigerant amount (kg) in the refrigerant system = Factory charged refrigerant (kg) for OU + Total additional amount of
charged refrigerant (kg) [= Additional charged refrigerant for OU +
Additional charged refrigerant for connecting pipe]
Factory charged refrigerant for outdoor unit :
AJ* 072L or AJ* 090L : 11.7 (kg)
AJ* 108L or AJ* 126L or AJ* 144L or AJ* 162L : 11.8(kg)
Check Item
Check contents
Judgement
Present Status
Ref. circuit name: ____________________________, Ref. address :________(00 99)
Outdoor Unit
3-way
valves
opening
3-way valve of each OU at
- Discharge pipe side
- Suction pipe side
- Liquid pipe side
Master OU ( all 3-way valve must be full open )
Yes / No
Slave-1 OU ( all 3-way valve must be full open )
Yes / No
Slave-2 OU ( all 3-way valve must be full open )
Yes / No
1-2-6 Refrigerant charge amount inspection sheet
1-2-7 3-way valve opening inspection sheet
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......