Heat Ex.1 gas temp. Error
Heat Ex.1 gas temp. sensor (TH7)
Heat Ex.1 gas temp. sensor (TH7) for use as condenser
(4way valve1:Off, EEV1:Open) is detected abnormally-low to
High pressure saturated temp. for 4 minutes or more.
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A 6. 3
Error Code : 9 U / A 6
1. Heat Ex.1 gas temp. sensor (TH7) not installed correct position.
2. Heat Ex.1 gas temp. sensor (TH7) defective
3. 4-way valve1 (including a coil) defective
4. EEV1 (including a coil) defective
5. Main PCB defective
Trouble shooting 66 EA6. 3
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
Check Point 1 : Check the condition of Heat Ex.1 gas temp. sensor (TH7)
Check the condition of mounting of Heat Ex.1 gas temp. sensor (TH7).
Check Point 3 : Check the condition of 4-way valve1 coil
Check the condition of mounting of 4-way valve1 coil and 4-way valve2 coil.
OK
Check Point 2 : Check the Heat Ex.1 gas temp. sensor (TH7)
Check characteristics check. (Disconnect the Heat Ex.1 gas temp. sensor from PCB and check.)
* For the sensor characteristics, refer to the "Service Parts Information 24".
OK
Check Point 4 : Check the EEV
Check the condition of mounting of EEV1 coil.
Check the connector connection state of EEV1, EEV2, EEV3 coil.
OK
Check Point 6 : Replace 4-way valve1
1. Fully close the 3-way valve, and the refrigerant is recovered.2. 4-way valve1 is replaced.
3. Perform vacuuming of repaired outdoor unit thoroughly , and add the refrigerant
with the recovered amount.
4. Check if the error reoccurs on a test run.
OK
OK
Check Point 5 : Replace Main PCB
Check the appearance and condition of mounting of Main PCB.
>> If it is abnormal, replace Main PCB.
(When Main PCB is replaced, set up the original setting by Rotary, Dip, and Push SW.)
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-78
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......