4-2 ABNORMAL OPERATION
4-2-1 Error code Display
1 4 . 3
Subsection Error Code
Specifics Error Code
14 : Network communication Error
3 : Indoor unit Network Communication Error
- Indoor unit (Operation / Timer / Filter) LED
- 2 / 3 Wires Remote controller
- Simple Remote controller
- Group Remote controller
- Central Remote controller
- Touch - Panel Controller
- Outdoor unit 7 segment Display
- Service Tool
An Error code is represented by 3 digit characters.
The first 2 digit means the subsection Error code, and the last 1 digit means the specifics Error code.
Ex.) Indoor unit Network communication Error
Each Error code section is shown by the following target
Subsection Error Code target
Subsection and Specifics Error code target
When an Error occurs, each devices indicate own abnormal detecting condtion.
In order to confirm the actual error condition, the following procedure are required.
1) Confirm the Specific Error code on the Outdoor unit 7 segment display or the Service tool.
Ex.1.) When the wired remote controller shows " 9 U (Outdoor unit Error)".
Ex.2*.) When the wired remote controller shows " 4 2 (Indoor unit Heat-Ex Sensor Error)"
2) Confirm each Error code on each devices in case of Network communication Error.
Ex.) When the Network cable of indoor unit 00 disconnected during operating
.
Operation LED: 1 time blinking
Timer LED: 4 times blinking
Error code “ 14.2 ”
Error code "14" “16”
Error code “14.1 or 14.3”
"Network communication Error"
*Indoor unit detects the condition of Error code 14.3,
but it can only display the Subsection Error code.
Outdoor unit
Service
Tool
Touch-panel Controller
Indoor unit 00
Indoor unit 01
Error code “ 14 ”
" No communication between
indoor unit 01 "
"14.1": No communication between Outdoorunit
and Service tool.
"14.3": Communication Error on the Indoor unit.
Wired remote
controller
Note: About Service tool
- To change the connecting location of service tool
can be helpful for the trouble shooting.
- To check the system configuration, the Address
checker function can be helpful for trouble shooting.
*The Specific Error code can be indicated by service tool.
- DipSW 4-2:ON Default Setting -
Error indication pattern
"14": Error on the Outdoorunit (14.2)
"16": The Communication Error between Touch-
panel controller and Error indoor unit.
Error indication pattern
04-03
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......