SERVICE PARTS INFORMATION 15
Outdoor Unit Electronic Expansion Valve
(EEV2)
Check Point 2 : Check Coil of EEV2
Remove connector, check each winding resistance of Coil.
If Resistance value is abnormal, replace EEV2.
Read wire
46 ± 4
Resistance value 68°F(20°C)
Check Point 1 : Check Connections
Check connection of connector (CN117)
(Loose connector or open cable)
Check Point 4 : Check Voltage from Controller PCB
Remove Connector and check Voltage (DC12V).
>> If it does not appear, replace Controller PCB.
Check Point 3 : Check Noise at start up
Turn on Power and check operation noise.
>> If an abnormal noise does not show, replace Controller PCB.
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in (1), but if there is a difference
as shown in (2), there is a possibility of inside clogged. In this case, replace Strainer.
Check Point 5 : Check Opening and Closing Operation of Valve
When EEV2 is closed,
it has no temp. difference between Inlet and Outlet.
If it is open, it has a temp. difference between Inlet and Outlet.
Outlet temp. is near Low-pressure saturated temp.
DC
Yellow - Red
Orange - Red
Blue - Red
White - Red
12V
Note : Check the EEV2 in the state of 4-way valve2 is ON.
In the following cases, even if EEV2 is closed, there may be a difference in temp.
- On comp. start-up
- Just after swiching the 4-way valve2
- Just after swiching the EEV2 (Open --> Close)
Note
If valve opening is 12~51pls,
the check of temp. cannot be performed.
Check temp. at the other valve opening.
CN160
CN116
CN117
CN1
17
04-118
Pipe (In)
Pipe (Out)
CLOSE
Pipe (In)
Pipe (Out)
OPEN
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
(1)
(2)
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......