1. Rotation obstructed by foreign matter
2. Ventilation obstructed by heat exchange foreign matter
3. Excessive ambient temperature rise
4. Static pressure setting incorrect, specifIed static pressure value exceeded
5. Driver PCB defective
Driver PCB
Check Point 1 : Check fan rotation state
Check for the absence of foreign matter around the fan
Check Point 2 : Check for obstruction of ventilation by heat exchange foreign matter
Check for foreign matter on heat exchanger
Check Point 5 : Replace Driver PCB
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check Point 4 : Check the static pressure
Check if static pressure is set correctly.
Check if static pressure is not higher than the specified value.
Check Point 3 : Check the ambient temperature
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 9 7. 5
Error Code : 9 U / 9 7
Outdoor Unit Fan Motor Temp.
Abnormal
Trouble shooting 55 E97. 5
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
1. When outdoor fan motor cannot operate more than 470rpm,
fan motor and compressor stops.
2. After fan motor restarts, if fan motor cannot operate at 470rpm or more,
or the same operation is repeated consecutively 3 times within 60 minutes,
fan motor and compressor stops permanently.
Check the appearance and condition of mounting of Driver PCB.
Change Driver PCB and release the error. Refer to the service parts info 5
Check if the error reoccurs on a test run.
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-67
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......