SERVICE PARTS INFORMATION 3
Main PCB
Filter PCB (Main)
Check Filter PCB (Main) -2
Check Filter PCB (Main) -1
Check Filter PCB (Main) -3
Replace Main PCB
Replace Main PCB
YES
YES
Check Main PCB -1
Replace Filter PCB (Main)
Replace Filter PCB (Main)
NO
YES
YES
Electric parts check
NO
Replace defective electric parts
YES
PCB pattern and parts on PCB defective?
Is Fuse (5A/ 250V) open?
(1) Replace blown fuse.
(2) Disconnect all the connection wires between the Filter PCB (Main) - Main PCB.
(3) Is there a short between L1-N, L3-N, and L1-L3?
(4) Connect all the connection wires between the Filter PCB (Main) - Main PCB
disconnected at step (2).
(5) The same as step (3), is there a short between L1-N, L3-N, and L1-L3?
(6) Are the following parts defective?
*For the check method, refer to 6-5.
- EEV
- SV
- 4-way valve
- Pressure sensor (High pressure/ Low pressure)
Check Main PCB -3
NO
NO
Check Main PCB -2
YES
(7) Disconnect the wires of the pressure sensors(High pressure/ Low pressure)
connected to the connector of the Main PCB.
(8) Is there a short between pins 1-3 of the Main PCB side connector?
(9) Is there a short between pins 1-6 of CN161?
Replace Main PCB
YES
Replace Main PCB
YES
NO
NO
NO
NO
Check Main PCB -4
(10) Disconnect the Main PCB side connector of the connection wires
(8-pin connector) between the Main PCB - Inverter PCB.
(11) Is there a short between pins 1-2 of the Main PCB side connector (8 pins)?
Turn on the power.
(14) Reconnect all the connection wires disconnected up to (1)-(13) to their original places.
(15) Turn on the AC power.
If the LED of the Main PCB does not light or blink, replaces the Main PCB, Filter PCB (Main).
Replace Main PCB
YES
NO
Check Main PCB -5
(12) Disconnect the Main PCB side connector of the connection wires
(6-pin connector) between the Main PCB - Fan driver PCB.
(13) Is there a short between pins 1-2 of the Main PCB side connector (6 pins)?
04-107
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......