01-05
Check Item
Check contents
Judgement
Present Status
Number of ref. circuit connected in the network system: ______, Ref. addresses: ______________(00 - 99)
VRF
Network
System
Transmission wire
Outlook
Is it LonWorks compatible?
Yes / No
Maker name?
Wire specification
0.33mm
2
, shield wire
(mm
2
)
Transmission line
connection points
Between Master OUs
Must be properly connected (Between Master OUs)
Master OUs Terminal: Z1 & Z2
Yes / No
Between Master OU &
Slave OU or
In between Salve OUs
Must be properly connected (Between Master OU and
Slave OU / Slave OU and Slave OU )
Terminal: H1 & H2
Yes / No
Shield wire connection Both ends of shield wire must be grounded
Yes / No
Wiring connection
Wiring connection per terminal ( 2)
Yes / No
1-2-4 Transmission wire installation inspection sheet 1/3
1-2-4 Transmission wire installation inspection sheet 2/3
Indoor unit
Outdoor unit (Master unit)
Refrigerant system
Check Item
Check contents
Judgement
Present Status
Number of ref. circuit connected in the network system: ______, Ref. addresses:_______________(00 99)
VRF Network
System
Network
wiring
Total transmission line length Wiring length 3600m
(Value taken from Network Design Drawing)
(m)
Network wiring layout
Do not make a loop configuration
Looped / Notlooped
No. of network segment
( * 1)
No. of network segment 41
( * 1)
Create one Network Segment based on the following conditions,
Condition -1: if the transmission line length 500m
Condition -2: if a total number of connected units
64 connected units
( * 2)
( *
2
)
connected units mean a total of ( Indoor Units + Master Outdoor Units
+ TPC Units + System Controller Units
+ Network Convertor for LonWorks Unit + Central RC Units + Network Convertor Units
+ BACnet Gateway Unit + Signal Amplifier Units + Service Tool Unit + Web Monitoring Tool Unit)
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......