03-09
3-2-7 "COOL" Position for Outdoor air unit
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
When using the cooling mode, set the temperature to a value lower than the discharge airflow temperature, otherwise
the outdoor air unit will not start the cooling operation and only the fan will rotate.
100%
0%
•
ON
•
Outdoor temp.
Ts : Corrected setting temperature
Ts - 5°C
Ts + 0.5°C : The thres hold temperature of start of refrigerant flow
Ts - 5°C : The thres hold temperature of stop of refrigerant flow
3-2-8 "HEAT" Position for Outdoor air unit
(1) When using the heating mode, set the temperature to a value higher than the discharge airflow temperature, otherwise
the outdoor air unit will not start the heating operation.
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation
will be temporarily interrupted.
Excess capacity area
Compressor ON
(6 minutes)
•
100%
0%
•
ON
•
Outdoor temp.
Ts : Corrected setting temperature
Ts +5°C
Ts - 0.5°C : The thres hold temperature of start of refrigerant flow
Ts + 5°C for 5 minutes or more
: The thres hold temperature of stop of refrigerant flow
Excess capacity area
Excess capacity area
Discharge airflow
Temperature
OFF
ON
OFF
Refrigerant
flow
Opening of
EEV
•
Ts
Outdoor air unit
fan
Compressor OFF
(3 minutes)
Compressor ON
(6 minutes)
5 minutes has passed
at excess capacity area
5 minutes has passed
at excess capacity area
Compressor ON
(6 minutes)
Compressor OFF
(3 minutes)
Compressor ON
(6 minutes)
(2)
Discharge airflow
Temperature
OFF
ON
OFF
Refrigerant
flow
Opening of
EEV
•
Ts
Outdoor air unit
fan
•
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......