01-22
1-8 Field Setting / Function Setting for Outdoor air unit
Setting Mode
ITEM
CODE No.
Setting Function
Default
Indoor unit field setting
Address
setting by
remote controller
01
Indoor unit address
00~63
00~63
00
02
Refrigerant circuit address
00~99
00~99
00
Filter
11
Filter indicator Interval
00
Default
01
Longer
02
Shorter
13
Filter sign display
00
Enable
01
Disable
02
Display only on central remote control
Airflow
Change of
Function 1
40
Auto restart *1
00
Enable
01
Disable
43
Cool air prevention
00
Super low
01
Follow the setting on the remote controller
46
External control
00
Start / Stop
01
Emergency stop
47
Error report target
63
Humidifier control *2
00
All
01
Display only for central remote control
ITEM
CODE No.
Classification
26
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
31
SP mode 05
SP mode 06
SP mode 07
SP mode 08
SP mode 09
SP mode 10
SP mode 11
SP mode 12
SP mode 13
SP mode 14
SP mode 15
SP mode 16
SP mode 17
SP mode 18
SP mode 19
SP mode 20
SP mode 21
SP mode 22
Normal SP
Static Pressure setting
- Outdoor air unit Only -
The Range of static pressure is
different from one model to other.
02
Foreced stop (Start/Stop by RC is restricted)
00
01
02
mode 00
mode 01
mode 02
*1: Auto restart is an emargency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Select control conditions of external output.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
Model name
ARXH054GTAH
ARQH140GTAH
ARXH072GTAH
ARQH224GTAH
ARXH096GTAH
ARQH280GTAH
Range of static
pressure
SP mode 05 to 19
(50 to 185 Pa)
SP mode 05 to 20
(50 to 200 Pa)
SP mode 05 to 22
(50 to 220 Pa)
Normal static
pressure
185 Pa
200 Pa
200 Pa
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......