OUTDOOR UNIT Error Method:
High Pressure Abnormal
1. 3-way valve not opened
2. Outdoor unit fan operation defective, foreign matter at heat exchanger, excessive ambient
temperature rise 3. EEV defective, strainer clogged
4. Solenoid valve defective 5. 4-way valve (including a coil) defective
6. Discharge pressure sensor defective 7. Refrigerant overcharged
Judgment from value sensed by discharge
pressure sensor
"Protection stop by "discharge pressure 580psi(4.00MPa)during operation of
any compressor"" generated 3 times within 60 minutes.
I
f the same operation (High pressure protection stop) generated 3 times
within 30 minutes, compressor stops permanently.
EEV operation check
Check of strainers before and after EEV
Refer to "Service Parts Information 13".
Check Point 3 : Check the EEV, strainer (indoor unit)
No foreign matter in air passage?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by effect of other heat sources?
Discharged air not sucked in?
Check Point 2 : Check the outdoor unit fan operation,
heat exchanger, ambient temperature
Discharge pressure sensor characteristics check
* For the characteristics of the discharge pressure sensor, refer to "Service Parts Information 22".
Check Point 6 :Check the discharge pressure sensor
Check Point 7 : Check the refrigerant amount
Refrigerant charged amount check
Check Point 5 : Check the solenoid valve (SV1, SV2)
Check Point 3 : Check the EEV, strainer
Solenoid valve operation check. Refer to "Service Parts Information 17".
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A 4. 1
Error Code : 9 U / A 4
OK
OK
OK
OK
OK
OK
Check Point 1 : Check if 3-way valve is open.
If the 3-way valve was closed, open the
3-way valve and check operation.
Check Point 1 : Check if 3-way valve is open.
If the 3-way valve was closed, open the
3-way valve and check operation.
OK
OK
Forecast of Cause :
Trouble shooting 63 EA4. 1
Indicate or Display:
Detective Actuators:
Detective details:
<Cooling
operation>
<Heating
operation>
EEV (EEV1, EEV2) open?
Strainer clogging check (before and after EEV, ACM, oil return)
Refer to "Service Parts Information 14, 15".
Check Point 4 : Check the 4-way valve (4WV1, 4WV2, 4WV3)
4-way valve operation check. Refer to "Service Parts Information 18".
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-75
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......