1. Stop the operation, and turn off the all outdoor units.
1-1. Backup operation when compressor of the master unit is defective.
[Procedure]
(Example: Three outdoor units are connected.)
2. Fully shut off the 3-way valve (Liquid, Gas) of the broken master unit.
3. Set the
Slave unit #1
as a new master unit, and make up the system of two outdoor units.
5. Uncouple the transmission connector between the broken master unit and indoor units,
and connect it into the slave unit #1 (substitutional master unit).
7. Turn on the units except the broken master unit, and wait for more than 30 seconds.
(Do not turn on the broken master unit)
8. It is ready for Backup operation.
Start operation as usual.
1. Method of backup operation
SERVICE INFORMATION
Backup Operation
4-4 SERVICE INFORMATION
Backup operation is the operating method of replacing compressor while the system is running.
Compressor can be replaced without stopping the system.
Details :
In backup operation, cooling and heating capacity is decreased by the capacity
of the separated outdoor unit.
The work procedure is as follows.
Change the setting of the DIP SW 3-1 / 3-2 (Outdoor unit address setting) of the slave
unit #1, from [ ](slave unit #1) to [ ](
Master unit
).
Change the setting of the DIP SW 3-3 / 3-4 (Number of slave units connected setting)
of the slave unit #1, from [ ](zero unit) to [ ](one unit).
6. Change the setting of the DIP SW 5-1/ 5-2 (Number of outdoor unit) of the slave unit #1 (substitutional
master unit) and #2 (substitutional slave unit #1), from [ON/ OFF](3) to [OFF/ ON](2).
4. Set up the
Slave unit #2
as the slave unit #1.
Change the DIP SW 3-1/ 3-2 (Outdoor unit address setting) of the slave unit #2,
from [ON/ OFF](slave unit #2) to [OFF/ ON](
Slave unit #1
).
4-4-1 Backup operation
OFF / ON
OFF / OFF
OFF / OFF
OFF / ON
( Make sure the pressure equalization has been finished.)
04-101
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......