2-4-2 Heating Operation
Fan step
16*
15
14
13
12
11
880
860
810
720
620
500
Fan speed (rpm)
intermittent 6
intermittent 5
intermittent 4
intermittent 3
intermittent 2
intermittent 1
6
5
4
3
2
1
Intermittent fan mode
Fan speed 0 rpm
duration time T ( sec )
Fan step
Fan mode
40
33
26
19
12
6
7
Fan speed 300 rpm
duration time ( sec )
When switched from normal fan step to intermittent fan step, always start from 300rpm/7sec.
When there was a change during intermittent step 1-6, switching is performed at the time the current speed
duration time reaches time-up.
7 sec
7 sec
7 sec
300 rpm
[ T ] sec
[ T ] sec
0 rpm
Normal fan step Intermitten fan step
Time
Fan speed
-20 21
( rpm )
Heating Operating range
( )
920
970
The fan speed during all heating is constant with
Fan step 16*
regardless of the outdoor air temperature.
(1) Heating Operation
880
920
870
820
720
620
500
970
870
820
720
620
500
AJ* 072/ 090L
AJ* 108/ 126L
AJ* 144/ 162L
AJ* 072/ 090L
AJ* 108/ 126L
AJ* 144/ 162L
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......