![Fujitsu AB* A12GATH Service Manual Download Page 134](http://html.mh-extra.com/html/fujitsu/ab-a12gath/ab-a12gath_service-manual_117995134.webp)
Liquid pipe temp. sensor 2
Liquid pipe temp. sensor 2 short or open detected
1. Connector connection defective, open
2. Sensor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the sensor
Sensor characteristics check (Disconnect the sensor from the PCB and check.)
* For the sensor characteristics, refer to the "Service Parts Information 24".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN142: 3-4) voltage value = 5V
Remove the sensor from Main PCB, check the voltage.
Liquid pipe temp. sensor 2 (CN142: 3-4)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 8 3. 2
Error Code : 9 U / 8 3
If the voltage does not appear, replace Main PCB and set up original address.
Liquid Pipe Temp. Sensor 2 Error
Trouble shooting 46 E83. 2
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
THERMISTOR (SC. INT. LIQ)
THERMISTOR (SC. EXT. LIQ)
THERMISTOR (SC. EXT. GAS)
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
CN142
04-58
OK
OK
DC
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......