OK
OK
Judgment from value sensed by current
sensor 1 (current sensor for inverter)
* Current sensor 1 is mounted on
Filter PCB(INV)
"Protection stop by "inverter speed 20rps and sensor value 0A continued
for 1 min"" was generated 2 times
Sensor value while inverter stopped = maximum was detected
1. Power supply defective
2. Power cable disconnection , open
3. Filter PCB (INV) to Inverter PCB CT system wiring connector disconnection, open
4. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
5. Filter PCB(INV) defective (Power supply section, current sensor section)
6. Inverter PCB defective
Check Point 2 : Filter PCB(INV) to Inverter PCB CT system wiring connection state
Connector and wiring connection state check
Cable open check
Connector connection state check
Cable open check
Chack Filter PCB (INV) and Inverter PCB.
(Refer to "Service Parts Information 4")
Check Point 4 : Check Filter PCB (INV) and Inverter PCB
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 8 4. 1
Error Code : 9 U / 8 4
Current Sensor 1 abnormal
Check Point 3 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
OK
Main power ON/OFF state check
Power cable connection, open check
Check Point 1 : Check the power supply
Trouble shooting 47 E84. 1
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-59
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......