Disponible en version courbe ?
non
Données techniques
Données techniques
Feeding
width
and
weight
are
shown
as
dimension
A
and
by
the
indications
of
the
table
of
references.
Encombrement
Poids
see table
Tension d'emploi
750V
Température d'utilisation
-30°C to +55°C
Calibre
100A, 130A, 160A, 200A-TR
Matière
Self-extinguishing thermoplastic, zinc coated steel
Fichier 3D à télécharger
http://catalogue.fels.fr/medias/produits/boite_d_alimentation_premontee_sur_element_droit.7z
Montage
Outils nécessaires au montage
Outils nécessaires au démontage
Règle d'installation 1
Fitted in place of a straight element. Provide a connecting box aside (not supplied). L = 4m: 3 sliding hangers. L = 1m: 2 sliding
hangers. Providing one or more feeding point in line rather than end-of-line reduces the voltage drop (?U = Lt.?3.Z.I) and allows to
choose a lower intensity because the length 'Lt' taken into account in the calculation varies according to the number of feed boxes.
Providing a feeding point midway in the line reduces by half the voltage drop, as the 'Lt' section taken into account is half the
length of the line. For more than one feeding point in line, please review the following graph for the position of the points and
related
voltage
drops.
www.fels.fr
|
T +33(0)3 88 67 10 60
|
F +33 (0)3 88 55 01 79
|
Edité le 04/01/2017
Page 73/223