Permissible Current according to Duty Cycle :
Intensity
315A
450A
630A
Rated Intensity
315A
450A
630A
Duty Cycle Factor for rated
intensity at 35°C
100%
100%
75%
Maximum permissible
current at 35°C for 100%
Duty Cycle
395A
500A
570A
Maximum permissible
current at 35°C for 80%
Duty Cycle
420A
540A
638A
Maximum permissible
current at 40°C for 100%
Duty Cycle
360A
460A
530A
Maximum permissible
current at 40°C for 80%
Duty Cycle
384A
495A
580A
Permissible Duty Cycle Factor according to the maximum operating temperature
θ
(°C)
315A
450A
630A
30
100%
100%
95%
35
100%
100%
75%
40
100%
100%
58%
45
100%
89%
44%
50
100%
67%
32%
55
76%
39%
22%
12.
LINE CALCULATION
See related section
(Data required for calculation, calculation method, charts...)
13.
ONLINE CALCULATION TOOL
See http://www.fels.fr/extranet/
(Online calculation with intensity suggested based on data submitted)
14.
COMPONENTS
See related section
(Straight elements, trolleys, feeding boxes...)
Horizontal curves: Curvature radius<15m, please inquire
15.
ASSEMBLY INSTRUCTIONS
See related section
Mobilis Movit Technical Data
www.fels.fr
|
T +33(0)3 88 67 10 60
|
F +33 (0)3 88 55 01 79
|
Edité le 04/01/2017
Page 158/223