13. VALUE OF THE RESISTANCE R AND OF THE RESISTANCE X
OF FAULT LOOP:
See EN60439-2 and CEI61439-6, below data for the application of the impedance method:
FAULT LOOP
Characteristics (Ω/m)
Intensity
130A
160A
200A - TR
R
b20ph ph
0,00101
0,000699
0,000505
R
b20ph N
0,00101
0,000699
0,000505
R
b20ph PE
0,00101
0,001048
0,000757
R
bph ph
(1)
0,00124
0,000865
0,000613
R
bph N
(1)
0,00124
0,000865
0,000613
R
bph PE
(1)
0,00124
0,001297
0,000919
X
bph ph
0,000271
0,000271
0,000271
X
bph N
0,000271
0,000271
0,000271
X
bph PE
0,000271
0,000271
0,000271
(1)
at 35°C ambient temperature and maximal rated current.
Protection against short-circuits:
For intensities
130A, Icw<10kA.
For intensities 160A and 200A TR: Ipk=11kA.
14. INTENSITY ACCORDING TO DUTY CYCLE:
ambiant
Temperature
Duty Cycle
Factor
Intensity
40A
60A
100A
130A
160A
200A
35°C
80%
72A
90A
117A
127A
162A
211A
40°C
80%
67A
86A
109A
117A
155A
195A
55°C
80%
48A
63A
86A
87A
131A
140A
35°C
100%
68A
85A
114A
120A
152A
184A
40°C
100%
64A
82A
106A
109A
145A
171A
55°C
100%
47A
61A
82A
83A
121A
126A
Mobilis Elite Technical Data
www.fels.fr
|
T +33(0)3 88 67 10 60
|
F +33 (0)3 88 55 01 79
|
Edité le 04/01/2017
Page 25/223