Données techniques
Données techniques
Capacity
of
the
terminal
block:
35mm²,
Tightening
capacity
of
the
cable
gland:
for
cables
Ø22
to
32mm.
Encombrement
Encombrement L x H x Z
164 x 195 x 375
Poids
1,7 kg
Tension d'emploi
750V
Température d'utilisation
-30°C to +75°C
Calibre
12A, 20A, 40A, 60A, 100A
Matière
Self-extinguishing thermoplastics, zinc coated steel
Montage
Outils nécessaires au montage
Outils nécessaires au démontage
Règle d'installation 1
Providing one or more feeding point in line rather than end-of-line reduces the voltage drop (?U= Lt.?3.Z.I) and allows to choose a
lower intensity because the length 'Lt' taken into account in the calculation varies according to the number of feed boxes. Providing
a feeding point midway in the line reduces by half the voltage drop, as the 'Lt' length taken into account equals half the length of
the line. For more than one feeding point in line, please review the following graph for the position of the points and related voltage
drops. With the version for curves, no limit for the radius at the curve-straight element junction, otherwise minimum radius R… at
the
curve-curve
junction.
www.fels.fr
|
T +33(0)3 88 67 10 60
|
F +33 (0)3 88 55 01 79
|
Edité le 04/01/2017
Page 69/223