9. SPACE REQUIREMENTS:
In addition to the space required for the various components (see in this section), make provision
for mounting/dismounting of electrical wiring.
10.
PROTECTION AGAINST FORGETTING:
Any connection, not fully established, prevents closing of covering flange, or of end-cap due to the
self-breaking screws.
11. OPERATING LIFE - ENDURANCE
The lines and accessories are built to withstand several years of use in a normal industrial
environment. The current collectors are designed to run for several thousand kilometers (see the
Maintenance section for recommended service schedule).
12.
RESISTANCE, REACTANCE, AND IMPEDANCE
UNDER NORMAL CONDITION
Impulse running:
When the rush of current is of short duration followed by long rest periods, the figures in the table
below can be used.
The value of the resistance R, reactance X and impedance Z at 50 Hz at ambient temperatures of
20°C and 35°C (short period current): the figures in the table are given in mΩ/m.
Intensity
12A
20A
40A
60A
100A
130A
160A
200A-TR
R
20
or R at 20°C
34,3
7,4
1,6
1,1
0,72
0,52
0,36
0,26
R (at 35°C)
35,8
8,1
1,69
1,16
0,76
0,55
0,38
0,27
R at 40°C
36,3
8,4
1,72
1,19
0,78
0,56
0,39
0,28
X
3,7
8,93
0,58
0,48
0,28
0,21
0,20
0,17
Z
20
or Z at 20°C
34,5
11,6
1,7
1,2
0,77
0,56
0,41
0,31
Z (at 35°C)
36
12,1
1,78
1,26
0,81
0,59
0,43
0,32
Z at 40°C
36,5
12,2
1,82
1,28
0,82
0,60
0,44
0,33
Mobilis Elite Technical Data
www.fels.fr
|
T +33(0)3 88 67 10 60
|
F +33 (0)3 88 55 01 79
|
Edité le 04/01/2017
Page 23/223