The intensity selected may be retained if the current in the line (IN) is lower than or equal to the
permissible intensity (I
adm
) :
I
N
I
adm
16.
LINES CALCULATION
See related section
(Data required for calculation, calculation method, charts...)
17.
ONLINE CALCULATION TOOL
See
http://www.fels.fr/extranet/
(Online calculation with intensity suggested based on data submitted)
18.
COMPONENTS
See related section
(Straight elements, trolleys, feeding boxes...)
19.
ASSEMBLY INSTRUCTIONS
See related section
20. SPECIAL RULES FOR STRAIGHT ELEMENTS WITH RIGID WIRING:
Reminder: Under normal conditions, no expansion joint is required for the installations according to
the table below.
Intensity
20A
40A
60A
100A
Max. length of line without expansion joint
140m
150m 150m 150m
However, in some cases the feeding boxes are connected with rigid cables preventing expansion,
which should then be considered as anchoring points. If such is the case, the following rules shall
apply.
Rules :
1. Placement of Fixed Hanger:
The anchoring points are to be located on the line element which is the closest to the connecting
box.
If some highly rigid cables are used preventing expansion, the anchoring points shall be located
close to line feeding:
2.
End-line Feeding
For lines longer than the lengths in the below table, an expansion joint will be required:
Intensity
12-20A
40A
60A
100A
130A
160A
200A-TR
Maximum Length
62m
76m
62m
52m
40m
35m
30m