Outputting diagnostics messages via the relay
You can output two categories of diagnostics messages via the relay:
1.
Diagnostics messages from one of the 4 Namur classes
(--> see the "Adjusting diagnostics information" section for more information on the
Namur classes)
2.
Diagnostics messages which you have individually assigned to the relay output
A message is individually assigned to the relay output at 2 specific points in the menu:
• Menu/Setup/General settings/Diagnostics/Device behavior
(device-specific messages)
• Menu/Setup/Inputs/../Diagnostics settings/Diag. behavior
(sensor-specific messages)
Before being able to assign a special message to the relay output in "Device behavior", you
must first configure Outputs/relay x:y or /Alarm relay/Function="Diagnostics".
Function="Diagnostics"
Function
Options
Info
Operating mode
Options
• as assigned
• Namur M
• Namur S
• Namur C
• Namur F
Factory setting
as assigned
as assigned
If this option is selected, the diagnostics messages which
you have individually assigned to the relay are output via
the relay.
Namur M... F
If you decided to use one of the Namur classes, all the
messages that are assigned to the individual class are
output via the relay.
You can also change the Namur class assignment for
every diagnostics message.
(Menu/Setup/General settings/Diagnostics/Device
behavior or Menu/Setup/Inputs/../Diagnostics
settings/Diag. behavior)
Attributed diagnostic
messages
Operating mode="as assigned"
Read only
List of diagnostic messages
All the messages assigned to the relay output appear on
the display.
You do not have the option of editing the information
here.