Doc
#
E154713
5-3
5: Communication Wiring
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
serial port on a computer or other device. The A7Z requires no power supply. All
power is received from the host computer serial port using transmitter and receiver
circuits within the probe. The RS232 standard limits the cable length to 50 feet
(15.2m).
A9U Instructions:
You need to download and install the driver for the A9U from EIG’s website:
www.electroind.com/A7Z_A9U.html. Once the driver is installed, attach the A9U’s
magnetic interface onto the meter’s Optical port and attach the A9U’s USB connection
into your PC.
Note that the Nexus® 1500+ meter’s optical port offers the standard inverted mode
for communication, but can also be programmed in non-inverted mode using the
Communicator EXT
TM
software. Refer to Chapter 11 in the
Communicator EXT
TM
4.0
and MeterManagerEXT Software User Manual
for instructions.
5.4: USB Connection
The USB connection allows the Nexus® 1500+ meter to communicate with a
computer that has a USB 1.1 or USB 2.0 Host port. The meter's USB port is config-
ured to operate as a virtual serial communication channel that the PC sees as a simple
COM port with a baud rate of up to 115200. The USB virtual serial communication
channel:
• Supports legacy applications that were designed to only work with a serial
communication channel
• Is compatible with standard USB cables that terminate with a USB Type B plug (see
Figure 5.2)
• The maximum length of the USB cable is 5 meters. Greater lengths require hubs or
active extension cables (active repeaters).
Figure 5.2: USB Type B Plug