12: Test Mode
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• To load a .csv file, click the Load button and locate the file you want to use.
14. When you have finished with the Test Mode Preset screen, click the X in the right
corner of the screen to close it.
15. When you want to exit Test Mode, click Tools>Set Test Mode to open the Test
Mode screen, and then click the Exit Test Mode button.
12.2.1.1: Alternative Methods of Updating Meter with Energy Presets
There are additional ways to update a meter with preset values.
When you enter the
preset values using the method just described, the values are saved in a file
(prstene.bin) which can be used to update the meter in one of the following ways.
This is useful if you have multiple meters to update - you can set up the preset values
once and then import the file into the other meters.
• Through the meter’s webpage: access the meter webpage (http://meter_ip_ad-
dress) and go to Tools>Energy Preset File Upgrade. Type the password information
and browse for the prstene.bin file to update to the meter. See section 20.1.18.1 in
the
Communicator EXT
TM
4.0 and MeterManager EXT Software User Manual
for
instructions.
• Through the Modbus holding registers. The file is divided into blocks of 64 bytes
each. The current file size for v1 is 1408 bytes, which contains 22 blocks. This
method is available to support any customized software application that uses the
energy preset values accessed through the Modbus registers. Follow this proce-
dure:
a. Start to send the file to the meter by writing the first block number (0x0000) to
Modbus address 0xAE00.
b. Write the block to Modbus register 0xAE01-0xAE20.
c. If all blocks have been written, then go to step e; otherwise continue to step d.
d. Continue to send the file to the meter by writing the next block number to
Modbus address 0xAE00. When finished writing the blocks, proceed to step e.
e. Compute the CRC-16 checksum for the entire file and write it to the Modbus
address 0xAE21