Doc
#
E154713
7-8
7: Transformer Loss Compensation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• Convert 1-Phase Watts Loss to 1-Phase kW by dividing the 1-Phase Watts Loss
by 1000.
4. Enter 3-Phase MVA or 1-Phase MVA values.
• If 3-Phase MVA values are entered, calculate 1-Phase MVA values by dividing 3-
Phase MVA values by three.
• Convert 1-Phase MVA to 1-Phase kVA by multiplying by 1000.
5. Enter the % Exciting Current and % Impedance values.
6. Enter the Phase-to-Phase values for Test Voltage (Volts) and Full Load Currents
(Amps). Note that Test Voltage is generally Phase-to-Phase for 3-Phase transform-
ers.
a. Calculate Phase-to-Neutral Test Voltage by dividing Phase-to-Phase Test Voltage
by the square root of 3.
b. Calculate Full Load Current (Amps) by dividing the 1-Phase kW self-cooled rating
by the Phase-to-Neutral Voltage and multiplying by 1000.
Value
3-Phase MVA
1-Phase MVA
1-Phase kVA
Self-Cooled Rating
% Exciting Current
% Impedance
Value
Phase-to-Phase
Phase-to-Neutral
Test Voltage (Volts)
Full Load Current (Amps)
Instrument Transformers
Numerator
Denominator
Multiplier
Potential Transformers
Current Transformers
Power Multiplier [(PT Multiplier) x (CT Multiplier)]