Doc
#
E154713
D-6
D: Using SNMP
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• SNMP Group - provides SNMP statistics as well as capability to enable SNMP
Traps.
• Transmission Group - provides device driver statistics for RS232 and Ethernet.
D.3.2: PDUs
PDUs, also referred to as “packets,” belong to one of two categories: PDUs sent from
the SNMP manager to the meter, and PDUs sent from the meter to the SNMP man-
ager.
• PDUs sent from the SNMP manager to the meter are:
• GetMessage (Message ID 0) - this retrieves the objects specified by the OIDs in
the message.
• GetNextRequest (Message ID 1) - this retrieves objects which are next in lexical
order in the MIB, to the objects specified by the OID in the message.
• GetBulkRequest (Message ID 5) - this retrieves a large number of objects speci-
fied by the OID in the message.
• SetRequest (Message ID 3) - this message modifies internal meter data specified
by an OID and value in the message.
• PDUs sent from the meter to the SNMP manager are:
• Response (Message ID 2) - this sends values in response to a GetRequest, Get-
NextRequest, GetBulkRequest, or SetRequest command.
• Trap (Message ID 4) - this is sent in response to predefined events (see D.3.3:
Summary of Contents for Shark 100T