Doc
#
E154713
D-12
D: Using SNMP
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
D.5: Modbus Map Location of SNMP Settings
The following table shows where in the Modbus map the SNMP settings from the
Device Profile are stored. For more information on the meter’s Modbus map, refer to
the Nexus® 1500+ Meter’s Modbus Manual.
SNMP Settings
Name
Settings
Description
Modbus
Device Profile
SNMP enable
0 = all interfaces disabled
1 = enable interface 1
2 = enable interface 2
3 = both interfaces enabled
Enable/Disable SNMP
service.
Refers Nexus 1500+
Network feature rev3
document
B3BCH
SNMP TRAPS enable
0 = all interfaces disabled
1 = enable interface 1
2 = enable interface 2
3 = both interfaces enabled
Enable/Disable TRAPS
service.
Refers Nexus 1500+
Network feature rev3
document
7614H
SNMP TRAPS Manager
1
0.0.0.0
1-8 IP addresses
75CCH –
75DBH
SNMP TRAPS
Bit 15:
1 (Enabled)
0 (Disabled)(Default)
Enable/Disable traps for
limits status changes
75F0H
Bit 14:
1 (Enabled)
0 (Disabled)(Default)
Enable/Disable traps for
digital input status
changes
Bit 13:
1 (Enabled)
0 (Disabled)(Default)
Enable/Disable traps for
waveform capture
Bit 12:
1 (Enabled)
0 (Disabled)(Default)
Enable/Disable traps for
PQ(CBEMA) event
Bit 11:
1 (Enabled)
0 (Disabled)(Default)
Enable/Disable traps for
relay output changes
Bit 10:
1 (Enabled)
0 (Disabled)(Default)
Enable/Disable traps for
transient capture
SNMP Agent Commu-
nity Name
20 bytes
“public”(default)
padding with null (0x00)
Expected community
name in input SNMP
GET, GETN and SET
messages.
75DCH-
75E5H
Summary of Contents for Shark 100T