Doc
#
E154713
11-19
11: Using the I/O Options
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
method is to attach the Din Rail clips to the mounting brackets to connect the I/O
modules to a DIN rail mounting system.
3. Starting with the left module and using a slotted screwdriver, fasten the first I/O
module to the left mounting bracket of the MBIO mounting brackets kit. The left
mounting bracket is the one with the PEM. Fasten the internal screw tightly into the
left mounting bracket.
4. Slide the female RS485 port into the male RS485 side port to connect the next
I/O module to the left module. Fasten together enough to grab but do not tighten,
yet.
5. Combine the modules together, one by one.
6. Attach a PSIO (power supply) to the right of each group of I/O modules it is supply-
ing with power (see Figure 11.6). The PSIO supplies 12 VA at 125 V AC/DC. See
sections 11.8.6 - 11.8.8 for I/O modules power requirements.
7. Once you have combined all of the I/O modules together for the group, fasten them
tightly. This final tightening locks the group together as a unit.
8. From the MBIO mounting brackets kit, attach the right mounting bracket to the
right side of the group using the small Phillips Head screws provided.
9. If not mounting on a DIN rail, mount the attached group of modules on a secure,
flat surface. This insures that all modules stay securely connected.
10. The MBIO mounting brackets kit comes with 2 DIN rail mounting clips and an
8mm screw and lock washer for each clip. The clips let you easily mount the
connected I/O modules (or a single I/O module between two brackets) on a DIN
rail. See the figure on the next page.
Summary of Contents for Shark 100T
Page 1: ...V 1 04 May 15 2018 ...