Doc
#
E154713
11-7
11: Using the I/O Options
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
EMC - Immunity Interference:
EN61000-4-2
Weight:
2.3 oz
Dimensions (inches) W x H x L:
0.75" x 4.02" x 5.49"
I/O card slot:
Option slot 2
Connection Type:
RJ45 modular (Auto-detecting
transmit and receive)10/100BaseT
OR
Duplex ST Receptacle - 100Base-FX
Fiber Optic Specifications are as follows:
Connector:
ST
Fiber Mode:
Multimode Fiber 62.5/125 um
Wavelength:
1310 nm
Max. Distance:
2 km
Default Configuration
The Nexus® 1500+ meter automatically recognizes the installed Option card during
power-up. If you have not programmed a configuration for the Ethernet card, the unit
defaults to the following configuration:
IP Address: 10.0.1.1
Subnet Mask: 255.255.255.0
Default Gateway: 0.0.0.0
NOTE
: The IP addresses of the Nexus® 1500+ meter's standard main Network card
and optional Network Card 2 must be in different subnets.