7: Transformer Loss Compensation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
11. Normalize Losses to Meter Nominal Power:
a. Enter Value at Trf Nominal for each quantity from previous calculations (step 10).
b. Enter Meter/Trf Value from Conversion Factors for Nominal Values (step 9).
c. Calculate M/T Factor w/Exp by raising the Meter/Trf Value to the power indicated
in Exp.
d. Calculate the Value at Meter Nominal by multiplying the M/T Factor w/Exp by the
Value at Trf Nominal.
12. Loss Watts Percentage Values: fill out the following section of the worksheet:
Meter Nominal kVA = 600 * (PT Multiplier) * (CT Multiplier) / 1000
= 600 * (____________) * (___________) / 1000
= ________________
13. Calculate Load Loss Values:
a. Enter Value at Meter Nominal from Normalize Losses (step 11).
b. Enter Meter Nominal kVA from previous calculation (step 12).
c. Calculate % Loss at Meter Nominal by dividing Value at Meter Nominal by Meter
Nominal kVA and multiplying by 100.
Quantity
Value at Meter
Nominal
Meter Nominal
kVA
% Loss at
Meter Nominal
Quantity
No-Load Loss
W (kW)
% Loss
Watts FE
No-Load Loss
VAR (kVAR)
% Loss
VARs FE
Full Load Loss
W (kW)
% Loss
Watts CU
Full Load Loss
VAR (kVAR)
% Loss
VARs CU