Chapter 5 List of Parameters
48
Function
code
number
Function code
name
Factory
setting
Setting range
Unit
Property
Function code selection
User
setting
frequency 1
(P0.13 ~ P0.14)
P4.23
Multi-section
frequency 2
8.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.24
Multi-section
frequency 3
10.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.25
Multi-section
frequency 4
15.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.26
Multi-section
frequency 5
18.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.27
Multi-section
frequency 6
20.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.28
Multi-section
frequency 7
25.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.29
Multi-section
frequency 8
28.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.30
Multi-section
frequency 9
30.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.31
Multi-section
frequency 10
35.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.32
Multi-section
frequency 11
38.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.33
Multi-section
frequency 12
40.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.34
Multi-section
frequency 13
45.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.35
Multi-section
frequency 14
48.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P4.36
Multi-section
frequency 15
50.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
Group P5 Multi-functional Input Parameter
P5.00
X1 terminal input
function selection
99
0 ~ 99
/
×
Refer to Definition of multi
function input terminals of P5
group in Chapter 6
P5.01
X2 terminal input
function selection
99
0 ~ 99
/
×
P5.02
X3 terminal input
function selection
99
0 ~ 99
/
×
P5.03
X4 terminal input
function selection
99
0 ~ 99
/
×
P5.04
X5 terminal input
function selection
99
0 ~ 99
/
×
P5.05
X6 terminal input
function selection
99
0 ~ 99
/
×
P5.06
X7/DI terminal input
function selection
99
0 ~ 99
/
×
P5.07
X1 to X7 terminal
filtering time
0.001
0.000 ~ 1.000 s
×
0.000 ~ 1.000s
P5.10
Maximum input
pulse frequency
10.0
0.1 ~ 50.0
kHz
×
0.1 ~ 50.0kHz
P5.11
Startup/stop mode
selection
0
0 ~ 3
/
×
0: 2-wire type 1;1: 2-wire type 2;
2: 3-wire type 1;3: 3-wire type 2;
P5.12
Preset counting
value reference
0
0 ~ 9999
/
×
0 ~ 9999
P5.13
Reached counting
value reference
0
0 ~ 9999
/
×
0 ~ 9999