Chapter 6 Parameter Description
119
6.17 Use of Display Parameters (Group d2)
Parameters in d2 group are read only parameters.
d2.09 indicates the input status of X terminal. 0 indicates Open, while 1 indicates Close. Hexadecimal
combination is adopted, and the lowest bit indicates X1.
d2.12 indicates the failure source of analog input. 1 indicates AI1 exceeding limit, 2 indicates AI2 exceeding
limit, 3 indicates AI3 exceeding limit, 4 indicates AV4/AI4 exceeding limit, and 5 indicates AV5/AI5
exceeding limit.Among them 4 and 5 only valid when use EX-PM01.
d2.13 indicates the current detection failure source display. 2 indicates phase W abnormal, 4 indicates
phase V abnormal, and 6 indicates phase U abnormal.
d2.14 indicates the frequency corresponding to the actual motor rotation speed under vector control 2 with
encoder speed feedback.
d2.00
Temperature of heatsink
0.0~100.0
º
C (0.0
º
C)
d2.01
Terminal count value
0~65535(0)
d2.02
AI1 percentage after curvilinear transformation
0.0~100.0%(0.0%)
d2.03
AI2 percentage after curvilinear transformation
0.0~100.0%(0.0%)
d2.04
AI3 percentage after curvilinear transformation
0.0~100.0%(0.0%)
d2.05
DI percentage after curvilinear transformation
0.0~100.0%(0.0%)
d2.06
Operation panel
∧/∨ digital adjustment volume
0~65535(0)
d2.07
Terminal UP/DN digital adjustment volume
0~65535(0)
d2.08
Reserved
0.00~65535(Factory)
d2.09
Input status display of X terminal
0~FFFF(0000)
d2.10
Reference voltage 1 (percentage)
0.0~100.0%(Factory)
d2.11
Reference voltage 2 (percentage)
0~9999(Factory)
d2.12
AI failure source display
0~5(Factory)
d2.13
Current detection failure source display
0~6(Factory)
d2.14
Frequency corresponding to the current rotation speed of
the motor
0.00~655.35Hz(0.00Hz)
d2.15~d2.24
Reserved
0~65535(Factory)