Chapter 6 Parameter Description
111
the inverter will be run after power resumes normal.
Note: To ensure this function is valid under terminal operating command reference mode, please do not
change the status of operating command terminal during shutdown.
When the inverter operates, the function can response the setting of reference channel for other
frequencies after using the pre-set frequency as the setting frequency and keeping the time as pre-set
frequency operating time Pb.18.
Temperature sensor
or analog signal
0
10V or 20mA
Low
Temperature
High
Sleeping
temperature
Operating
temperature
Setting
frequency
Output
frequency
Pb.19
Pb.20
Fig. 6-35 Upper and lower limit of zero frequency operation
This function supports sleep function and energy saving operation. After running, the inverter will start
when the setting frequency
≥Pb.19. During operation, the inverter operates at zero frequency
when the
setting frequency
≤Pb.20. Proper setting of limit value of zero operation can avoid the inverter starting
and stopping frequently. If the inverter is often used for work situations such as air condition and fan,
change the analog signal of temperature sensor to setting frequency to control automatic starting or
stopping of inverter. See Fig. 6-35.
Parameters copy function can be realized through operation panel.
0: No operation. When upload or download completed, the parameter restores automatically to 0.
1: Upload parameters. Press PRG button to upload parameters to the operation panel after setting, and
will display percentage of copy process when indicating “LoAd”.
Pb.17
Pre-set frequency
0.00~300.00 Hz(0.00Hz)
Pb.18
Pre-set frequency operating time
0.0~3600.0 s(0.0s)
Pb.19
Upper limit of zero frequency operation
0.00~300.00 Hz(0.00Hz)
Pb.20
Lower limit of zero frequency operation
0.00~300.00 Hz(0.00Hz)
Pb.23
Parameters copy
0~5(0)
Pb.21
Reserved
0~1(0)
Pb.22
Reserved
0.0~380.0(380.0)