Chapter 6 Parameter Description
95
FDT level lower limit
Output frequency
Tim
e
Yi terminal
Time
FDT level upper limit
Fig.6-29: Frequency level detection signal (FDT)
It controls the action of the multifunctional input terminal or output terminal by the host computer.
Display of operation panel
Unit place
Multifunctional input terminal Xi
0: The real terminal is enabled;
1: The virtual terminal is enabled
Tens place
reserved
Hundreds
place
Y1, Y2 and relay terminals
0: The real terminal is enabled;
1: The virtual terminal is enabled
When Xi terminal signal source is input as virtual terminal, whether the corresponding function of this
terminal is effective depends on the control of the host computer and has nothing to do with the real
status of the current Xi terminal.
When Yi, Y2 and relay terminals are output as virtual terminals, the real outputs of these terminals
depend on the control of the host computer and have nothing to do with whether the output terminal
function set is effective.
It defines the validity of the input and output status of the multifunctional digital terminals.
Display of operation panel
Unit place
Multifunctional input terminal Xi
0: Current through Xi is valid;
1: No current through Xi is invalid
Tens place
Multifunctional output terminal Yi
0: Current through Yi is valid;
1: No current through Yi is invalid
Hundreds
place
Relay output terminal
0: Enable in magnetizing status;
1: Enable in no magnetizing status
When the digital input Xi terminal and COM terminal are short circuited, it may judge whether the input
P7.24
Virtual terminal effective selection
000 ~ 111(000)
P7.25
Terminal effective status selection
000 ~ 111(000)