Chapter 5 List of Parameters
46
Function
code
number
Function code
name
Factory
setting
Setting range
Unit
Property
Function code selection
User
setting
P2.02
Display parameter
selection at running
1CB0
0 ~ FFFF
/
○
LED ones place:
0: Reference frequency (Hz);
1: Bus voltage (V);
2: AI1(V); 3: AI2(V);
4: AI3(V); 5: DI (%);
6: External counting;
7: Motor rotation speed (rpm);
8: Close loop reference (%);
9: Close loop feedback (%);
A: Reference torque (%);
B: Running frequency (Hz);
C: Output current (A);
D: Output torque (%);
E: Output power (kW);
F: Output voltage (V);
LED tens, hundreds, thousands
place: Same with above
P2.03
Display parameter
selection at stopping
3210
0 ~ FFFF
/
○
LED ones place:
0: Reference frequency (Hz);
1: Bus voltage (V);
2: AI1(V);
3: AI2(V);
4: AI3(V); 5: DI (%);
6: External counting;
7: Motor rotation speed (rpm);
8: Close loop reference (%);
9: Close loop feedback (%);
A: Reference torque (%);
B: Reserved;
C: Reserved;
D: Reserved;
E: Reserved;
F: Reserved;
LED tens, hundreds, thousands
place: Same with above
P2.04
Running proportion
display benckmark
0
0 ~ F
/
○
0 ~ F
P2.05
Running proportion
display coefficient
0.0
0.0 ~ 1000.0
%
○
0 ~ 1000.0%
P2.06
Stopping proportion
display benckmark
0
0 ~ F
/
○
0 ~ F
P2.07
Stopping proportion
display coefficient
0.0
0.0 ~ 1000.0
%
○
0 ~ 1000.0%
Group P3 Start/stop Parameter
P3.00
Startup mode
0
0 ~ 2
/
×
0: Normal startup;
1: Start after DC injection;
2: Flying startup
P3.01
DC injection current 0.0
0.0 ~ 120.0
%
×
Constant torque: 0.0 ~ 120.0%
inverter rated current
Variable torque: 0.0 ~ 90.0%
inverter rated current
P3.02
DC injection time
0.00
0.00 ~ 30.00
s
×
0.00 ~ 30.00s
P3.03
Startup frequency
0.50
0.00 ~ 60.00
Hz
×
0.00 ~frequency upper limit the
lower of P0.13 and 60.00Hz
P3.04
Startup frequency
retention time
0.0
0.0 ~ 3600.0
s
×
0.0 ~ 3600.0s
P3.05
Stop mode
0
0 ~ 2
/
×
0: Deceleration to stop;
1: Coast to stop;
2: Deceleration to stop+DC braking