Chapter 6 Parameter Description
81
3: Terminal reverse run input (REV)
The functions of above items 0 to 3 are only enabled in the terminal running command reference mode
(P0.06=1). Interlocking of running command and jog command means that the jog command will not be
executed in the running status and the running command will not be executed in the jog status.
4: Three-line running control
It is only enabled in the terminal running command reference mode ((P0.06=1). Refer to P5.11 for the
instructions about its application.
5: Pulse frequency DI input (only available for X7/DI terminal)
When the pulse frequency DI input acts as the reference (e.g. P0.04=4 or P1.02=4), this function must be
selected for the X7/DI terminal.
6: Multi-section digital voltage terminal 1
7: Multi-section digital voltage terminal 2
8: Multi-section digital voltage terminal 3
Refer to P4.15 ~ P4.21 for the instructions about its application.
9: Multi- section frequency terminal 1
10: Multi- section nt frequency terminal 2
11: Multi- section frequency terminal 3
12: Multi- section frequency terminal 4
Refer to P4.22 ~ P4.36 for the instructions about its application.
13: Acceleration/deceleration time terminal 1
14: Acceleration/deceleration time terminal 2
Refer to the table below for the instructions about its application.
Acceleration/deceleration
terminal 2
Acceleration/deceleration
terminal 1
Acceleration/deceleration time
selection
OFF
OFF
Acceleration/deceleration time 0
OFF
ON
Acceleration/deceleration time 1
ON
OFF
Acceleration/deceleration time 2
ON
ON
Acceleration/deceleration time 3
15: Digital regulating frequency reset
It is used to reset the change values of the setup frequency regulated by the operation panel
∧/∨ and
terminal UP/DN. When this terminal is enabled, the operation panel
∧/∨ and term inal
UP/DN are
disabled.
16: Frequency increase command
17: Frequency decrease command
The two terminals are used to modify the setup frequency with UP/DN key.
18: Acceleration/deceleration disable command
If this terminal is enabled, the running frequency will remain unchanged unless stop command is
executed.