11 Troubleshooting & Maintenance
Symptom
Probable Cause
Possible Solution
Slave devices on the master
side of the open circuit con-
tinue to communicate; how-
ever, the slaves on the far
side do not communicate.
One or both conductors in the
RS-485 bus are broken.
Open Circuit, check RS-485
connection.
TXD LED does not flash
Incorrect hardware configura
-
tion.
Hardware failure.
Reconfigure hardware.
Repair or replace hardware.
TXD LED flashes, RXD LED
doesn’t.
There’s a problem in the com-
munications channel connect-
ing the PC to the LED.
Trace the signal from the com-
munications channel to the
meter. Determine where the
signal is being interrupted and
correct the problem.
Data rate or frame mismatch.
Frequency variation is
higher than expected.
VR terminal is floating.
Wire VR terminal to earth/
ground reference.
Default “admin” and “X”
UserID/Password sets do
not work.
UserID/Password forgotten.
Remove the tamper seal-
able security cover from the
PXPS-1 or PXPS-4 card.
Move the Mode 1 and Mode
2 switches to the OFF posi-
tion. Cycle power to the meter.
Login as “ADMIN” with the
“ADMIN” password within 15
minutes. Setup new adminis-
trator-level UserID/Password.
Return to secure mode with
the Mode 1 or Mode 2 switch
in the ON position. Reinstall
the tamper sealable security
cover. Reboot the meter.
Cannot connect over the
LAN/WAN Ethernet.
Duplicate IP Address.
Network requires a Domain
name
PC arp table contains an old
MAC Address for the given IP
Use DHCP to automatically
assign a unique IP address.
Once a Domain name is ac-
quired, turn off the automatic
setting and enter the Domain
Name setting.
Clear the PC’s arp table (e.g.,
arp-d
on the Windows com-
mand prompt).
Summary of Contents for Power Xpert PXM 4000
Page 1: ...User and Installation Manual IM02601004E Power Xpert PXM 4000 6000 8000 ...
Page 8: ...Page vi IM02601004E www eaton ...
Page 19: ...www eaton com IM02601004E Page 11 1 Introduction ...
Page 24: ...Page 16 IM02601004E www eaton ...
Page 36: ...Page 18 IM02601004E www eaton com 2 Quick Start Guide for the Meter Module ...
Page 45: ...www eaton com IM02601004E Page 37 3 Installation 3 8 MeterDimensions ...
Page 46: ...Page 38 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 47: ...www eaton com IM02601004E Page 39 3 Installation Dimension Con t ...
Page 48: ...Page 40 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 53: ...www eaton com IM02601004E Page 45 3 Installation ...
Page 54: ...Page 46 IM02601004E www eaton 3 Installation ...
Page 55: ...www eaton com IM02601004E Page 47 3 Installation ...
Page 56: ...Page 48 IM02601004E www eaton 3 Installation ...
Page 57: ...www eaton com IM02601004E Page 49 3 Installation ...
Page 58: ...Page 50 IM02601004E www eaton 3 Installation ...
Page 59: ...www eaton com IM02601004E Page 51 3 Installation ...
Page 60: ...Page 52 IM02601004E www eaton 3 Installation ...
Page 61: ...www eaton com IM02601004E Page 53 3 Installation ...
Page 62: ...Page 54 IM02601004E www eaton 3 Installation ...
Page 63: ...www eaton com IM02601004E Page 55 3 Installation ...
Page 66: ...Page 58 IM02601004E www eaton 3 Installation ...
Page 75: ...www eaton com IM02601004E Page 67 4 Introduction to Web Server Screens ...
Page 76: ...Page 68 IM02601004E www eaton 4 Introduction to Web Server Screens ...
Page 86: ...Page 78 IM02601004E www eaton 5 Introduction to the Local Graphical Display ...
Page 108: ...Page 100 IM02601004E www eaton 6 Functions on the Web Server Pages ...
Page 128: ...Page 120 IM02601004E www eaton 7 Functions on the Graphical Display ...
Page 164: ...Page 156 IM02601004E www eaton 8 Setup on the Web Server Pages ...
Page 198: ...Page 190 IM02601004E www eaton A MODBUS Communication ...
Page 242: ...Page 234 IM02601004E www eaton ...
Page 252: ...Page 244 IM02601004E www eaton D Diagnostics ...
Page 254: ...Page 246 IM02601004E www eaton D Diagnostics ...