8 Setup on the Web Server Pages
SUBCYCLE DISTURBANCE
The Power Xpert Meter captures subcycle disturbances with its regular metering hardware, which
samples at 30.72 ksps. You can set the dv/dt Threshold and Absolute Threshold for Van, Vbn, Vcn,
Vab, Vbc, and Vca. In addition, you can select the kind of action that will occur when one of the
thresholds has been reached; Capture Waveform, Capture Parameters and/or Send E-mail.
The Absolute Threshold Voltage setting is intended
to trigger on Voltage spikes that exceed the normal
positive and negative peak values, which are typi-
cally 1.4 times the rms line-to-ground Voltage. It is
important to set this threshold safely above the ex-
pected peaks. The Setup page suggests a threshold
that is 20% above the Nominal L-L Voltage (divided
by the PT ratio). For example, a 120V/208V system
has a 120V rms and 170V peak (line-to-ground), and
so a 250V threshold is appropriate (i.e. 208 + 20%).
The dv/dt Threshold setting is entered in dv while the
dt is fixed at the hardware sampling rate. The Setup
page suggests an aggressive threshold. Specifically,
the setup page suggests a threshold that is 5% of
the Nominal L-L Voltage (divided by the PT ratio).
To calculate the volts per microsecond, multiply the threshold Volts by 0.03072. For example, if the
dv/dt Threshold is set at 20V, the Volts per micro second would be 0.744 (i.e. 20V x 0.0372 Msps =
0.744 V/ microsecond).
A 30.72 ksps sampling rate and a pure 120V sine wave would result in a dv of 1.5V per sample at
the zero crossing. A disturbed waveform would have a much higher dv/dt.
Note:
To notify Power Xpert software of subcycle disturbances, select the Send Web Services
Notification box.
Summary of Contents for Power Xpert PXM 4000
Page 1: ...User and Installation Manual IM02601004E Power Xpert PXM 4000 6000 8000 ...
Page 8: ...Page vi IM02601004E www eaton ...
Page 19: ...www eaton com IM02601004E Page 11 1 Introduction ...
Page 24: ...Page 16 IM02601004E www eaton ...
Page 36: ...Page 18 IM02601004E www eaton com 2 Quick Start Guide for the Meter Module ...
Page 45: ...www eaton com IM02601004E Page 37 3 Installation 3 8 MeterDimensions ...
Page 46: ...Page 38 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 47: ...www eaton com IM02601004E Page 39 3 Installation Dimension Con t ...
Page 48: ...Page 40 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 53: ...www eaton com IM02601004E Page 45 3 Installation ...
Page 54: ...Page 46 IM02601004E www eaton 3 Installation ...
Page 55: ...www eaton com IM02601004E Page 47 3 Installation ...
Page 56: ...Page 48 IM02601004E www eaton 3 Installation ...
Page 57: ...www eaton com IM02601004E Page 49 3 Installation ...
Page 58: ...Page 50 IM02601004E www eaton 3 Installation ...
Page 59: ...www eaton com IM02601004E Page 51 3 Installation ...
Page 60: ...Page 52 IM02601004E www eaton 3 Installation ...
Page 61: ...www eaton com IM02601004E Page 53 3 Installation ...
Page 62: ...Page 54 IM02601004E www eaton 3 Installation ...
Page 63: ...www eaton com IM02601004E Page 55 3 Installation ...
Page 66: ...Page 58 IM02601004E www eaton 3 Installation ...
Page 75: ...www eaton com IM02601004E Page 67 4 Introduction to Web Server Screens ...
Page 76: ...Page 68 IM02601004E www eaton 4 Introduction to Web Server Screens ...
Page 86: ...Page 78 IM02601004E www eaton 5 Introduction to the Local Graphical Display ...
Page 108: ...Page 100 IM02601004E www eaton 6 Functions on the Web Server Pages ...
Page 128: ...Page 120 IM02601004E www eaton 7 Functions on the Graphical Display ...
Page 164: ...Page 156 IM02601004E www eaton 8 Setup on the Web Server Pages ...
Page 198: ...Page 190 IM02601004E www eaton A MODBUS Communication ...
Page 242: ...Page 234 IM02601004E www eaton ...
Page 252: ...Page 244 IM02601004E www eaton D Diagnostics ...
Page 254: ...Page 246 IM02601004E www eaton D Diagnostics ...