www.eaton.com
IM02601004E
Page 141
8 Setup on the Web Server Pages
Use the Edit button at the bottom of the page to modify current settings. The page will display 8
digital inputs. Use the scroll bar on the right side of the page to view additional digital inputs.
Use the ID text box to name the digital input if desired. Use the drop down box beside the ID to
select the function (Counter, Status, Demand Sync, DCF 77, and Disable) of each digital input.
Additional information may be required for some functions. For example, if Counter is selected,
Pulse Weight, Pulse Multiplier, and Units must be entered. If Status is selected, the Delay time in
seconds, the polarity of the input, and the triggering behavior must be set. In addition, the output
settings, Log Event, Capture Waveform, and/or Send e-mail must be entered. Click the OK button
at the bottom of the page when entry is complete.
INTERNAL I/O OUTPUT SETUP
The Output section of the Internal I/O contains three separate relay pages, R1, R2, and R3. Each
of these pages list the relay’s ID, Mode, Trigger Type, Trigger, and Duration. You can associate
each relay with up to 16 triggers. The Trigger Types are dictated by entries in previous setup pages.
There are nine possible triggers types available to you; Out of Limits, ITIC Alarms, Subcycle Distur-
bance, Fast Transient, Demand Overload, Input Status, Modbus Triggered, and End of Interval.
If one of these setup pages is not completed or selected, the option will not be available in the drop
down box for Trigger Type. If triggers are established for Out of Limits, Alarms and Demand Over-
load, these options will be available in the Trigger Type drop down box.
The Trigger drop down boxes provide options relative to the Trigger Type only. For example, if you
select Out of Limits as the Trigger Type, the Trigger options will be restricted to the triggers set up
in the Out of Limits setup page, such as: Phase AB Line - Line Voltage, System Real Power, etc. If
the trigger is not setup in the previous page, it will not be available for selection in this page.
One of the three modes; Latched, Timed, or Normal could be selected for a relay output.
• In Latched mode, the relay is energized when a selected event occurs. The relay stays energized
until it is reset manually.
• In Timed mode, the relay is energized for the duration specified when the event occurs.
• In Normal mode, the relay is energized when the event occurs and de-energized when the event
is reset. Duration specifies the minimum time the relay will stay energized after recognizing the
event.
Locating Internal I/O Output Setup on the Web
From the Setup Main Page, select Meter Setup & Commissioning from the tree structure on the left
side of the page. The tree structure will expand to list Security, I/O, Clock, Communications, and
System. Click I/O. The tree structure will expand to list Pulse Initiation, Internal I/O and Remote
I/O. Click Internal I/O. The tree structure will expand to list Inputs and Outputs. Click Outputs. The
tree structure will expand to list the three relays: RY1, RY2, and RY3. When a relay is selected, the
page will update to display the current relay trigger settings. Use the Edit button at the bottom of
the page to modify the current settings. All 16 triggers cannot be viewed at once. Use the scroll bar
on the right side of the page to view additional settings that may not be displayed.
Use the ID text box to name the relay output, if desired. Use the drop down box below the ID to
select the Trigger Type and the Trigger from the options available. After these options are selected,
choose the Mode from the drop down box and enter the duration. To add additional triggers for
this relay, click the Add Trigger button at the top right of the page. Use the Delete button beside
the Trigger to remove the Trigger Type from the relay. Click the Done button at the top of the page
when entry is complete.
Summary of Contents for Power Xpert PXM 4000
Page 1: ...User and Installation Manual IM02601004E Power Xpert PXM 4000 6000 8000 ...
Page 8: ...Page vi IM02601004E www eaton ...
Page 19: ...www eaton com IM02601004E Page 11 1 Introduction ...
Page 24: ...Page 16 IM02601004E www eaton ...
Page 36: ...Page 18 IM02601004E www eaton com 2 Quick Start Guide for the Meter Module ...
Page 45: ...www eaton com IM02601004E Page 37 3 Installation 3 8 MeterDimensions ...
Page 46: ...Page 38 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 47: ...www eaton com IM02601004E Page 39 3 Installation Dimension Con t ...
Page 48: ...Page 40 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 53: ...www eaton com IM02601004E Page 45 3 Installation ...
Page 54: ...Page 46 IM02601004E www eaton 3 Installation ...
Page 55: ...www eaton com IM02601004E Page 47 3 Installation ...
Page 56: ...Page 48 IM02601004E www eaton 3 Installation ...
Page 57: ...www eaton com IM02601004E Page 49 3 Installation ...
Page 58: ...Page 50 IM02601004E www eaton 3 Installation ...
Page 59: ...www eaton com IM02601004E Page 51 3 Installation ...
Page 60: ...Page 52 IM02601004E www eaton 3 Installation ...
Page 61: ...www eaton com IM02601004E Page 53 3 Installation ...
Page 62: ...Page 54 IM02601004E www eaton 3 Installation ...
Page 63: ...www eaton com IM02601004E Page 55 3 Installation ...
Page 66: ...Page 58 IM02601004E www eaton 3 Installation ...
Page 75: ...www eaton com IM02601004E Page 67 4 Introduction to Web Server Screens ...
Page 76: ...Page 68 IM02601004E www eaton 4 Introduction to Web Server Screens ...
Page 86: ...Page 78 IM02601004E www eaton 5 Introduction to the Local Graphical Display ...
Page 108: ...Page 100 IM02601004E www eaton 6 Functions on the Web Server Pages ...
Page 128: ...Page 120 IM02601004E www eaton 7 Functions on the Graphical Display ...
Page 164: ...Page 156 IM02601004E www eaton 8 Setup on the Web Server Pages ...
Page 198: ...Page 190 IM02601004E www eaton A MODBUS Communication ...
Page 242: ...Page 234 IM02601004E www eaton ...
Page 252: ...Page 244 IM02601004E www eaton D Diagnostics ...
Page 254: ...Page 246 IM02601004E www eaton D Diagnostics ...