www.eaton.com
IM02601004E
Page 149
8 Setup on the Web Server Pages
the performance of the Display Link. Modbus modes 3 and 4 allow you to automatically split the
requests between the the two ports, depending on the slave device address. These are “load
balancing” options as all Display Link address fall in the lower part of the range, and are therefore
automatically routed to a particular RS485 port using these modes.
Modbus Timeouts
The following explains the Modbus timeout settings, and how to use them. These two settings com-
bine to create a total timeout period (in ms) that equals the following formula:
Total Timeout = Subnet Timeout X (Subnet Retries value + 1)
If a subnet device doesn’t respond within the Total Timeout, the meter responds with exception 11
(0xb) or “Gateway Target Device Failed to Respond.”
Subnet Timeout
This is the timeout value (or amount of time permitted for a subnet device to
respond to a command).
The default value is 1000 ms.
This can also be set via
Modbus register 2005.
Subnet Retries
The number of times the meter will retry a subnet command before issuing.
The
default value is 0
(or, “only try once”).
Modbus Subnet Gateway Configuration
The Subnet Mode field controls how the meter behaves as a Modbus subnet gateway. See page
6A-25 for instructions on configuring the RS485 ports (COM1, or if the Communications Adapter is
installed, COM2.)
0
Setting the Subnet Mode to zero disables the meter from functioning as a Subnet Gateway
Master. It will only respond to Modbus commands sent to its own slave address. The local ad-
dress is the base address set by the hex switch.
1 This is the default setting for COM1
. Setting Subnet Mode to 1 enables the meter as a
Modbus Subnet Gateway Master. This is the default setting for Com1The meter will route any
commands to slave addresses (other than its own) to the RS485/RS-232 port set as a Master-
Gateway. If no response is received from the slave device within the total timeout (specified
above), the meter returns an exception 11 (0xB) “Gateway Target Device Failed to Respond.”
If no RS-485 port is currently set as the Master-Gateway, the meter returns an exception 10
(0xA) “Gateway Path Unavailable.”
2 This is the default setting for Com2.
Setting the mode to 2 also enables the meter as a
Modbus Subnet Gateway Master. This is the default setting for Com2. The meter will route any
commands to slave addresses (other than its own) to the RS485/RS232 port set as a Master-
IO. If no response is received from the slave device within the total timeout (specified above),
the meter returns an exception 11 (0xB) “Gateway Target Device Failed to Respond.” If no
RS485/RS232 port is currently set as the Master-IO, the meter returns an exception 10 (0xA)
“Gateway Path Unavailable.”
3
This is a load balancing option that requires that the optional Communications Expansion card
has been installed. Unlike Subnet Gateway Master modes 1 and 2, the Gateway will route any
commands to slave address (other than its own) to one of the RS485/RS232 ports, depending
on the address. Slave addresses of 127 or below are routed to the RS485 port configured as a
Master-IO while slave addresses of 128 or above are routed to the Master -Gateway.
As with the other Subnet Gateway Master Modes, if no response is received from the slave
device within the total timeout (specified above), the meter returns an exception 11 (0xB)
“Gateway Target Device Failed to Respond.” If no RS-485 or RS232 port is currently set as
either the Master-Gateway or Master-IO, the meter returns an exception 10 (0xA) “Gateway
Path Unavailable.”
4
This is another “load balancing” option that requires that the optional Communications Expan-
sion card has been installed. The Gateway will route any commands to slave address (other
than its own) to one of the RS485 or RS232 ports, depending on the address. Slave addresses
Summary of Contents for Power Xpert PXM 4000
Page 1: ...User and Installation Manual IM02601004E Power Xpert PXM 4000 6000 8000 ...
Page 8: ...Page vi IM02601004E www eaton ...
Page 19: ...www eaton com IM02601004E Page 11 1 Introduction ...
Page 24: ...Page 16 IM02601004E www eaton ...
Page 36: ...Page 18 IM02601004E www eaton com 2 Quick Start Guide for the Meter Module ...
Page 45: ...www eaton com IM02601004E Page 37 3 Installation 3 8 MeterDimensions ...
Page 46: ...Page 38 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 47: ...www eaton com IM02601004E Page 39 3 Installation Dimension Con t ...
Page 48: ...Page 40 IM02601004E www eaton 3 Installation Dimension Con t ...
Page 53: ...www eaton com IM02601004E Page 45 3 Installation ...
Page 54: ...Page 46 IM02601004E www eaton 3 Installation ...
Page 55: ...www eaton com IM02601004E Page 47 3 Installation ...
Page 56: ...Page 48 IM02601004E www eaton 3 Installation ...
Page 57: ...www eaton com IM02601004E Page 49 3 Installation ...
Page 58: ...Page 50 IM02601004E www eaton 3 Installation ...
Page 59: ...www eaton com IM02601004E Page 51 3 Installation ...
Page 60: ...Page 52 IM02601004E www eaton 3 Installation ...
Page 61: ...www eaton com IM02601004E Page 53 3 Installation ...
Page 62: ...Page 54 IM02601004E www eaton 3 Installation ...
Page 63: ...www eaton com IM02601004E Page 55 3 Installation ...
Page 66: ...Page 58 IM02601004E www eaton 3 Installation ...
Page 75: ...www eaton com IM02601004E Page 67 4 Introduction to Web Server Screens ...
Page 76: ...Page 68 IM02601004E www eaton 4 Introduction to Web Server Screens ...
Page 86: ...Page 78 IM02601004E www eaton 5 Introduction to the Local Graphical Display ...
Page 108: ...Page 100 IM02601004E www eaton 6 Functions on the Web Server Pages ...
Page 128: ...Page 120 IM02601004E www eaton 7 Functions on the Graphical Display ...
Page 164: ...Page 156 IM02601004E www eaton 8 Setup on the Web Server Pages ...
Page 198: ...Page 190 IM02601004E www eaton A MODBUS Communication ...
Page 242: ...Page 234 IM02601004E www eaton ...
Page 252: ...Page 244 IM02601004E www eaton D Diagnostics ...
Page 254: ...Page 246 IM02601004E www eaton D Diagnostics ...