Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
NOTE
The load connector breaker controls the load connector only, not the output power cord.
2.
Press any button on the front panel display to activate the menu options. Select TURN UPS ON/OFF,
TURN UPS OFF, and press the
button.
3.
Confirm the selection. Press and hold the
button for three seconds, until the UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and the
indicator turns off.
4.
Switch the UPS battery circuit breaker to the OFF (O) position.
5.
If optional EBMs are installed, switch all EBM battery circuit breakers to the OFF (O) position.
6.
Switch the UPS input circuit breaker to the OFF (O) position.
7.
Switch off utility power where the UPS is connected.
55..1122
IInnddiivviidduuaall P
Paarraalllleelleedd U
UP
PS
S S
Shhuuttddoow
wnn
To shut down an individual UPS in the parallel system (see
) :
1.
Switch the load connector circuit breaker to the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power cord.
2.
Press any button on the front panel display to activate the menu options. Select TURN UPS ON/OFF,
TURN UPS OFF, and press the
button.
3.
Confirm the selection. Press and hold the
button for three seconds, until the UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and the
indicator turns off.
4.
Switch the UPS battery circuit breaker to the OFF (O) position.
5.
If optional EBMs are installed, switch all EBM battery circuit breakers to the OFF (O) position.
6.
Switch the UPS input circuit breaker to the OFF (O) position.
7.
Disconnect the redundant signal cable(s) from the UPS.
8.
If you are shutting down all the UPSs in a parallel system, repeat Steps 1 through 7 for each UPS then
remove utility power from the system. Otherwise, continue to Step 9.
9.
If it is necessary to completely remove power from the individual UPS (without shutting down all UPS
modules) disconnect the individual UPS from the BladeUPS Bar.
55..1133
P
Paarraalllleelleedd S
Syysstteem
m S
Shhuuttddoow
wnn
To remove power to the parallel UPS system output (see
) :
1.
Switch each UPS load connector circuit breaker to the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power cord.
2.
Press any button on any front panel display to activate the menu options. Select TURN UPS ON/OFF,
TURN SYSTEM OFF, and press the
button.
3.
Confirm the selection. Press and hold the
button for three seconds, until the UPS stops beeping.
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...