Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
UPSs in a parallel configuration require a dedicated branch circuit that meets the following requirements:
•
Three-phase, 4-wire plus ground, 208Y/120V nominal (BladeUPS 12 model) or 400Y/230V nominal, 380–
415 Vac acceptable (BladeUPS 12i model)
•
50/60 Hz
•
Wall-mounted breaker that is readily accessible to the operator
•
Flexible or rigid metal conduit
•
Circuit with overcurrent protection, depending on parallel configuration (see Table 2 )
Table 2. BladeUPS Overcurrent Protection
Number of UPSs in Preassembled System
BladeUPS 12 Model
BladeUPS 12i Model
1
50A
30A
2
100A
63A
3
150A
75A
4
200A
100A
5
225A
125A
6 (N+1 System)
225A
160A
NOTE
For ease of wiring access with bottom entry, place the rack containing the UPSs on a
raised floor.
33..99
P
Prreeppaarriinngg tthhee R
Raacckk
Preparing the Rack
To prepare the rack for wiring:
1.
Remove the accessory box that is located in the rear of the system behind the rack doors.
2.
Verify that the following items are in the accessory box:
•
UPS documentation and software tools:
–
Software Suite CD and this user’s guide
–
BladeUPS: Documents, Firmware, and Installation Video CD
•
(2) Door Keys
•
CAN Bridge Card accessories:
–
(1) CAN Bridge Card Cable
–
(1) Redundant Signal Cable
•
Optional X-Slot card accessories
The preassembled system can be ordered with any of the optional X-Slot cards installed. Accessories
for installed cards are in the accessory box.
lists the cards and the associated accessories.
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...