Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
39
To install the parallel system input and output wiring:
1.
Verify that all battery circuit breakers on all UPSs are in the OFF (O) position (see
).
Figure 20. BladeUPS Module Rear Panel
Load
(RPM) Connector
Breaker
Input
Breaker
Battery
Breaker
2.
Remove the five screws on the bottom entry wireway access cover and retain. Remove the cover and
retain (see
).
Figure 21. Removing the Wireway Access Cover (Bottom Entry Rack Shown)
3.
Remove the six screws on the conduit landing plate and retain. Remove the plate and retain. See
.