Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
83
NOTE
Installing one Eaton® Power Xpert® Gateway card allows you to communicate with all
UPS modules connected to the same parallel bus configuration.
17. If you left the UPSs unattached to the rack, secure the front and rear of each UPS as described in step 14
and 15 .
18. If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the ground cable
(not included) to the ground bonding screw.
19. You can install an optional REPO circuit that will shut down the entire parallel system using a single switch.
To install the REPO switch before powering on the parallel system.
20. Connect the parallel input cord from each paralleled UPS, as shown in
.
•
Loosen the two screws on the plug retainer and slide the plug retainer out.
•
Gently loop and twist the parallel input cord as shown to minimize stress on the cord. The loop and
twist for each cord may vary depending on configuration and strain relief to the BladeUPS Bar in the
rack.
•
Insert the parallel input cord into the socket. The plug is fully seated when the plug latches snap (top
and bottom) into place.
NOTE
Make sure the connectors are snapped in tightly to prevent incorrect system operation.
•
Slide the plug retainer back in and tighten the screws.
NOTE
The plug retainer prevents the plug from being inadvertently unplugged.
21. Continue to section
“Parallel Initial System Startup”.
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...