140
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Table 25. Electrical Output (Continued)
BladeUPS 12 Model
BladeUPS 12i
Model
BladeUPS 8 Model
BladeUPS 5.0
Model
Short Circuit Capability
(Normal Mode)
Limited by 50A input
breaker
Limited by 30A input
breaker
Limited by 50A input
breaker
Limited by 50A input
breaker
Nominal Output Frequency
50–60 Hz auto-detection (Normal mode)
50 or 60 Hz (Battery mode)
Output Frequency Variation
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
Output Overload
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Voltage Waveform
Standard mode and Battery mode: Sine wave; <2% THD with linear load;
<5% with nonlinear load
Full Output
Three-phase
Table 26. Environmental and Safety
BladeUPS 12 Model
BladeUPS 12i
Model
BladeUPS 8 Model
BladeUPS 5.0
Model
Surge Suppression
ANSI C62.41 Category
B3
EN 61000-4-6
ANSI C62.41
Category B3
ANSI C62.41
Category B3
Safety Conformance
UL 1778 4
th
edition;
CSA C22.2, No. 107.3
UL 1778 4
th
edition,
EN and IEC 62040-1-1
UL 1778 4th edition;
CSA
C22.2, No. 107.3
UL 1778 4th edition;
CSA
C22.2, No. 107.3
Agency Markings
cULus, ICES, CE
cULus, CE
cULus
cULus
EMC (Class A)
FCC Part 15
EN 62040-2
FCC Part 15
FCC Part 15
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 5°C to 25°C (41°F to 77°F)
Storage Temperature
0°C to 25°C (32°F to 77°F)
Transit Temperature
-25°C to 55°C (-13°F to 131°F)
Relative Humidity
Operating: 5–95% noncondensing
Non-operating: 5–95% relative humidity, 38.7°C (101.7°F)
Maximum wet bulb temperature with no cosmetic damage
Operating Altitude
Up to 1,000 meters (3,300 ft) above sea level;
up to 2,000 meters (6,600 ft) with 1% derating per +100 meters (330 ft)
Transit Altitude
Up to 15,000 meters (49,000 ft) above sea level
Heat Dissipation
1432 BTU in HE, 4094
BTU Standard mode
539 BTU in HE, 4000
BTU Standard mode
902 BTU in HE, 3066
BTU Standard mode
673 BTU in HE, 2217
BTU Standard mode
Audible Noise
Less than 58 dBA at 1 meter typical (Normal mode)
Less than 64 dBA at 1 meter typical (Battery mode)
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...