Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
139
Table 24. Electrical Input
BladeUPS 12 Model
BladeUPS 12i Model
BladeUPS 8 Model
BladeUPS 5.0
Model
Nominal Voltage
120/208V three-phase
230/400V three-phase
120/208V three-phase
120/208V three-phase
Nominal Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Frequency Range
45–65 Hz
45–65 Hz
45–65 Hz
45–65 Hz
Default Frequency
Auto-detected
Auto-detected
Auto-detected
Auto-detected
Rated Input Current
36A
24A
24A
16A
Connections
IEC 309-60A power
cord
IEC 309-32A power
cord
NEMA L21-30P
NEMA L21-20P
Paralleling available for 12 kW or 12i kW
modules only. For paralleling, a single Anderson
input/output cord connects to the
BladeUPS Bar (see
).
BladeUPS 8 and BladeUPS 5.0 kW cannot be
paralled
NOTE:
BladeUPS 8 kW can be upgraded in the
field to 12 kW in order to be paralleled for
additional capacity. Contact Eaton service for
details.
Noise Filtering
MOVs and common mode line filter
Input Power Factor
High Efficiency setting: load dependent
Standard setting: >0.99
Input Mode
Three-phase
Input Source
5-wire with continuous neutral.
NOTE:
Contact your Eaton UPS sales specialist for operation with 4-pole ATS switches.
Table 25. Electrical Output
BladeUPS 12 Model
BladeUPS 12i
Model
BladeUPS 8 Model
BladeUPS 5.0
Model
Nominal Output Voltage
120/208 Vac three-phase
230/400 Vac three-
phase
120/208V three-
phase
120/208V three-
phase
Output Voltage Variation
104–132 Vac phase to
neutral,
180–229 Vac phase to
phase
207–253 Vac phase
to neutral,
358–438 Vac phase
to phase
104–132 Vac phase
to neutral,
180–229 Vac phase
to phase
104–132 Vac phase
to neutral,
180–229 Vac phase
to phase
Connections
IEC 309-60A power cord
IEC 309-32A power
cord
NEMA L21-30R
NEMA L21-20R
Paralleling available for 12 kW or 12i kW
modules only. For paralleling, a single Anderson
input/output cord connects to the
BladeUPS Bar (see table 19 on Page 136 )
.
BladeUPS 8 and BladeUPS 5.0 kW cannot be
paralled
NOTE:
BladeUPS 8 kW can be upgraded in
the field to 12 kW in order to be paralleled
for additional capacity. Contact Eaton service
for details.
Short Circuit Capability
(Battery Mode)
84A, <300 ms
44A, <300 ms
84A, <300 ms
84A, <300 ms
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...